Direct in-situ measurement
The sensor is installed at or in the process to reduce sample-transport delay.
An inline analyser intended for direct supervision of hazardous gas concentrations in industrial processes.
TINA InSituAn inline analyser intended for direct supervision of hazardous gas concentrations in industrial processes.
An in-situ or inline analyser concept for direct monitoring of toxic and process gases without a conventional extractive sample line.
The measuring principle, gas path and sample conditioning are selected for the application.
The sensor is installed at or in the process to reduce sample-transport delay.
Sensor, range and hazardous-area configuration are selected for the target gas and location.
Measurement results can support process optimisation, reporting, quality control and designed alarm functions.
Direct measurement shortens the path between the process and detector.
Continuous values can support leak and threshold supervision.
The inline concept avoids a conventional extractive conditioning train where suitable.
The final configuration depends on gases, ranges, sample conditions and system integration.
The range and final configuration are confirmed for the medium and process conditions.
| Current product name | TINA InSitu |
|---|---|
| Function | In-situ / inline gas monitoring without extractive sample transport |
| Measured components | CH₄, KWL and other configuration-specific toxic, process or VOC gases |
| Application | Direct process, safety and leak monitoring |
| Configuration | Sensor, range, hazardous-area approval and interfaces are selected for the measuring task |
| Technology | Diffusion measurement with NDIR photometer and reference detector |
| Range | Up to 100% LEL, gas-dependent |
| Accuracy | Below 2% of measured value and below 1% full scale |
| Response time | T50 below 5 s; T90 below 10 s |
| Automatic zero correction | Included |
| Process pressure | 0.9–1.1 bar |
| Operating temperature | 0–70 °C, non-condensing |
| Housing / chamber | Aluminium IP67 housing; stainless-steel measuring chamber |
| Power / readiness | 24 VDC, 55 VA ±10%; approx. 5 min, full specification after approx. 30 min |
Key information for design, commissioning and subsequent analyser operation.
Accessibility, gas representativeness and process exposure must be assessed.
Approval and installation requirements are selected for the plant zone.
The design must allow safe inspection and sensor replacement.
Provide the key measurement information. MES-EKO will check the instrument configuration and required sampling components.