Chemical plants and process installations
Monitoring at several points around process equipment with detectors selected for the gases present.
The control panel receives signals from gas detectors, displays their readings and controls alarms. It supports 4 detectors as standard and up to 8 with an expansion board.
CE408Panel and detector selection depends on the hazard, number of points and required system response.
Monitoring at several points around process equipment with detectors selected for the gases present.
Centralised readings from detection points and alarm signalling to the site system.
Alarm signalling from detectors around fuel installations.
Assigning alarms to monitored points or zones.
Centralised display and alarm outputs for installations with several detection points.

The large backlit display shows live readings from connected detectors. Use the keypad for local operation and programming.
Three password-protected access levels help separate permissions. A list of preset Tecnocontrol detectors simplifies input configuration.
The panel checks whether input and output boards are present. Firmware can be updated from an SD card.
The ES404 and ES414 boards can be selected independently, with a maximum of one of each type. The input count determines the number of detectors the panel can handle; the gas measured depends on the connected detector.
+4 detector inputs · 4–20 mA
Expands the panel from 4 to 8 detector inputs. Maximum one ES404 per panel. Check compatibility and follow the CE408 documentation for installation and configuration.
+4 relay outputs
Expands the panel from 5 to 9 relay outputs. Maximum one ES414 per panel. Select and configure the output functions according to the documentation for the specific panel.
Three programmable thresholds and a fault indication distinguish gas alarms from faults. Thresholds can be programmed by zone.
Within a zone, AND requires all assigned conditions to be met; OR requires at least one. PARKING is intended for car park applications and must be selected to suit the installation design.
RESET clears indications as configured. Green, yellow and red LEDs show panel status. The display shows the last 100 events; the clock adjusts automatically for daylight saving time.
| Power supply | 230 V AC |
|---|---|
| Detector inputs | 4 detector inputs, 4–20 mA; up to 8 with ES404 |
| Logic input | 1, for triggering an immediate alarm |
| Relay outputs | 5, up to 9 with ES414 |
| Relay contact rating | 3 A resistive load, SPDT, 230 V AC |
| Alarm thresholds | 3 programmable + fault |
| Dimensions (W × H × D) | 285 × 230 × 140 mm |
| Ingress protection | IP54 |
| Input expansion | ES404 – 4 additional 4–20 mA inputs |
| Output expansion | ES414 – 4 additional relay outputs |
| Backup power (optional) | 2 × 12 V / 1.3 Ah |

The panel receives signals from suitable 4–20 mA detectors, including compatible SE and TS models. Relay outputs can signal alarms or faults to external equipment through a compatible contact input.
Potential example: Tecnocontrol GDS850. Before connecting, verify the 4–20 mA output type and scaling, wiring, detector supply and current demand, and how the panel interprets fault and service signals.

Leave the panel accessible for operation and servicing. Select the location to suit the environment, the IP54 enclosure rating and safe cable routing.
Document channel, threshold and output assignments. Check the complete signal path: detector response, alarm and fault signalling, and the response of controlled equipment. Set the inspection and calibration schedule using the documentation and site procedures.
Detector ATEX or SIL markings do not extend to the panel or complete installation. Assess safety requirements for the full function, including its inputs, logic and final elements.
We can help turn your installation requirements into a CE408 panel configuration.
Integration depends on the specific device version, electrical parameters, signal range and scaling, and required alarm functions. Verify the configuration before selecting devices.
Tell us the target gas, installation location and alarm requirements. We can help select the device and plan the integration.