TECNOCONTROL · MES-EKO

CE408 — gas detection control panel

The control panel receives signals from gas detectors, displays their readings and controls alarms. It supports 4 detectors as standard and up to 8 with an expansion board.

Tecnocontrol CE408 – front view of the control panelCE408
4 → 8 inputs4–20 mA signal
5 → 9 relaysOutputs for alarm signalling
3 thresholds + faultConfigurable thresholds
Local panelBacklit display and keypad
100 eventsEvent history view

Industrial applications

Panel and detector selection depends on the hazard, number of points and required system response.

Chemical plants and process installations

Monitoring at several points around process equipment with detectors selected for the gases present.

Biogas and wastewater treatment plants

Centralised readings from detection points and alarm signalling to the site system.

Power generation and boiler rooms

Alarm signalling from detectors around fuel installations.

Warehouses and technical facilities

Assigning alarms to monitored points or zones.

Multipoint monitoring

Centralised display and alarm outputs for installations with several detection points.

CE408 Design and Operation

Tecnocontrol CE408 with front-panel display and keypad
Front panel: display, keypad and status LEDs.

Display and keypad

The large backlit display shows live readings from connected detectors. Use the keypad for local operation and programming.

Access levels and detector setup

Three password-protected access levels help separate permissions. A list of preset Tecnocontrol detectors simplifies input configuration.

Board checks and updates

The panel checks whether input and output boards are present. Firmware can be updated from an SD card.

Standard configuration and expansion

Standard configuration

  • 4 4–20 mA detector inputs
  • 5 relay outputs
  • 1 logic input for triggering an immediate alarm

Expanded configuration

  • 8 detector inputs with the ES404 board (+4 inputs, 4–20 mA)
  • 9 relay outputs with the ES414 board (+4 relays)
  • 1 logic input, unchanged

The ES404 and ES414 boards can be selected independently, with a maximum of one of each type. The input count determines the number of detectors the panel can handle; the gas measured depends on the connected detector.

CE408 expansion modules

ES404Detector input expansion module

+4 detector inputs · 4–20 mA

Expands the panel from 4 to 8 detector inputs. Maximum one ES404 per panel. Check compatibility and follow the CE408 documentation for installation and configuration.

ES414Relay output expansion module

+4 relay outputs

Expands the panel from 5 to 9 relay outputs. Maximum one ES414 per panel. Select and configure the output functions according to the documentation for the specific panel.

Alarm logic

Thresholds and zones

Three programmable thresholds and a fault indication distinguish gas alarms from faults. Thresholds can be programmed by zone.

AND, OR and PARKING

Within a zone, AND requires all assigned conditions to be met; OR requires at least one. PARKING is intended for car park applications and must be selected to suit the installation design.

RESET, LEDs and history

RESET clears indications as configured. Green, yellow and red LEDs show panel status. The display shows the last 100 events; the clock adjusts automatically for daylight saving time.

CE408 technical specifications

Power supply230 V AC
Detector inputs4 detector inputs, 4–20 mA; up to 8 with ES404
Logic input1, for triggering an immediate alarm
Relay outputs5, up to 9 with ES414
Relay contact rating3 A resistive load, SPDT, 230 V AC
Alarm thresholds3 programmable + fault
Dimensions (W × H × D)285 × 230 × 140 mm
Ingress protectionIP54
Input expansionES404 – 4 additional 4–20 mA inputs
Output expansionES414 – 4 additional relay outputs
Backup power (optional)2 × 12 V / 1.3 Ah
Front and side views of the CE408 enclosure
Illustrative enclosure views. See the table for CE408 dimensions.

Integration with detectors and alarm systems

  1. Gas detectors
  2. 4–20 mA inputs
  3. CE408
  4. Alarm relays
  5. Actuating devices

The panel receives signals from suitable 4–20 mA detectors, including compatible SE and TS models. Relay outputs can signal alarms or faults to external equipment through a compatible contact input.

Potential example: Tecnocontrol GDS850. Before connecting, verify the 4–20 mA output type and scaling, wiring, detector supply and current demand, and how the panel interprets fault and service signals.

Installation and safety

Tecnocontrol control panel enclosure shown open for service access
The hinged enclosure allows access during installation and servicing.

Installation location

Leave the panel accessible for operation and servicing. Select the location to suit the environment, the IP54 enclosure rating and safe cable routing.

Commissioning and periodic checks

Document channel, threshold and output assignments. Check the complete signal path: detector response, alarm and fault signalling, and the response of controlled equipment. Set the inspection and calibration schedule using the documentation and site procedures.

Safety assessment scope

Detector ATEX or SIL markings do not extend to the panel or complete installation. Assess safety requirements for the full function, including its inputs, logic and final elements.

Technical selection

CE408 — gas detection system selection with MES-EKO

We can help turn your installation requirements into a CE408 panel configuration.

What we review

  • Detection pointsSelect detectors and the number of inputs to suit the installation layout.
  • Thresholds and outputsDefine which events should trigger an alarm or an equipment response.
  • Expansion and integrationCheck whether expansion boards are needed and how signals should be passed on.

Related devices

Integration depends on the specific device version, electrical parameters, signal range and scaling, and required alarm functions. Verify the configuration before selecting devices.

Selection and integration with MES-EKO

Tell us the target gas, installation location and alarm requirements. We can help select the device and plan the integration.