Cold rooms and storage
Point leak detection near refrigeration equipment, with the gas and range selected for the refrigerant in use.
A fixed detector with an integrated sensor and no display. It sends readings to a control panel or monitor via 4–20 mA or Modbus RS-485, depending on the ordered version.
GDR300For installations where readings are viewed at a control panel and the detector is required to transmit a measurement signal without a local screen.
Point leak detection near refrigeration equipment, with the gas and range selected for the refrigerant in use.
Sending readings over 4–20 mA or RS-485; the correctly configured supervisory system provides the alarm response.
Sensing and electronics share one unit. Its position must suit both the detection point and the sensor operating conditions.
GDR300 provides 4–20 mA and Modbus RS-485 according to the ordered configuration. It does not have the voltage outputs or relays found on GDR4xx models.
LEDs indicate operating status. On Bluetooth-equipped versions, the app provides local configuration and diagnostics; it does not replace the permanent alarm path.
Cartridge and checks. The replaceable cartridge stores sensor identification and calibration data. Replacement requires the manufacturer’s procedure and suitably trained personnel. A bump test checks gas response; it does not replace calibration. Zero and span calibration must only be performed where permitted for the particular cartridge, using the correct gas and instructions. Check intervals depend on the sensor and operating conditions.
| Gas / refrigerant | Version code | Technology | Measuring range |
|---|---|---|---|
| NH₃ | GDR300EA / GDR300EAH | Electrochemical | 0–1000 / 0–100 ppm |
| CO₂ | GDR300IC25 / IC210 / IC220 / IC250 | NDIR | 0–5000 ppm / 0–1 / 0–2 / 0–5 vol.% |
| R290 / R600 | GDR300I1 / GDR300I2 | NDIR | 0–100% LFL |
| R290 / R600 | GDR300PP / GDR300PG | Pellistor | 0–100% LFL |
| R407C, R410A, R507A, R449A, R32, R134a, R404A, R1234ze, R1234yf, R454B, R454C | GDR300I3–I13 | NDIR | 0–2000 ppm |
| R407C, R410A, R507A, R449A, R32, R134a, R404A, R1234ze, R1234yf, R454B, R454C | GDR300S3–S13 | MOS | 0–1000 ppm |
Each detector is selected for one gas and range; this table does not describe a single multi-gas device. The shortened IC210, IC220 and IC250 codes have the same model prefix as IC25. I3–I13 and S3–S13 map to gases in the order listed in each row. PX/IX/SX versions for other gases require manufacturer confirmation.
| Sensor | Integrated in the enclosure |
|---|---|
| Technologies | Electrochemical, NDIR, MOS or pellistor — gas- and code-specific |
| Display | None; LED indication |
| Primary signal | 4–20 mA |
| Communication | RS-485 / Modbus, Bluetooth — according to version |
| Voltage output | None |
| Relays | None |
| Low-voltage supply | 11–30 V DC / 12–24 V AC (+10 / −15%) |
| Enclosure | IP67 |
| EC sensor — operating limits | EA / EAH: approximately 2 years; −40 to +50°C. |
| NDIR sensor — operating limits | Approximately 5 years in clean air according to manual rev. E. Codes IC25 / IC210 / IC220 / IC250 and I1–I9: −40 to +60°C. |
| Pellistor — operating limits | Approximately 5 years. PX: −40 to +60°C; temperature limits for other codes are confirmed separately. |
| MOS sensor — operating limits | Approximately 5 years. Codes S3–S9 and SX: −20 to +50°C according to the cartridge table in manual rev. E. |
Based on the GDR manual, revision E, April 2026, and manufacturer version tables. Confirm RS-485 and Bluetooth fitment for the order code. GDR300 does not have voltage outputs, relays or an audible sounder.
These are indicative clean-air lifespans, not warranty periods. Actual life depends on the gas, exposure, contamination and operating conditions. Temperature limits for I10–I13, S10–S13 and other special versions are confirmed during selection. Interface and output availability depends on the complete ordering code. The configuration is confirmed during product selection.
Choose GDR300 for an integrated sensor and transmission of readings to a system. Consider GDR400 for relays, or GDR450 for a local display.
Compare the five GDR detectors by sensor location, display and outputs.
Selection requires checking the gas, range, power supply and signal scaling. Detector location, alarm thresholds, gas response checks and calibration must follow the documentation and site procedures. IP67 is not an ATEX or SIL designation. Measuring R290 or R600 in %LFL does not automatically approve the detector for installation in an explosive atmosphere.
Tell us the refrigerant, sensing location and required alarm response. We help select equipment for the installation.
Describe the installation requirements. Inquiry for: GDR300.