Refrigeration plant rooms
Detection of a selected gas around refrigeration units and pipe connections, with signals sent to the alarm system.
An integrated-sensor detector without a display for refrigeration leak monitoring. Its versions offer analogue and digital outputs and relays, depending on the configuration.
GDR400A choice of signal options when a local screen is unnecessary but readings or alarms need to be sent to the installation.
Detection of a selected gas around refrigeration units and pipe connections, with signals sent to the alarm system.
Monitoring a hazard point using analogue output, Modbus or relays as provided by the selected version.
4–20 mA is the primary output. Suitable versions provide 1–5 V or 2–10 V, RS-485/Modbus, two alarm relays and one fault relay.
LEDs indicate device status. Bluetooth, where fitted to the ordered version, provides configuration and diagnostics through an app close to the detector.
The sensor and electronics share one enclosure. Where the sensing point must be separate, GDR403 is the remote-sensor counterpart.
Cartridge and checks. The replaceable cartridge stores sensor identification and calibration data. Replacement requires the manufacturer’s procedure and suitably trained personnel. A bump test checks gas response; it does not replace calibration. Zero and span calibration must only be performed where permitted for the particular cartridge, using the correct gas and instructions. Check intervals depend on the sensor and operating conditions.
| Gas / refrigerant | Version code | Technology | Measuring range |
|---|---|---|---|
| NH₃ | GDR400EA / GDR400EAH | Electrochemical | 0–1000 / 0–100 ppm |
| CO₂ | GDR400IC25 / IC210 / IC220 / IC250 | NDIR | 0–5000 ppm / 0–1 / 0–2 / 0–5 vol.% |
| R290 / R600 | GDR400I1 / GDR400I2 | NDIR | 0–100% LFL |
| R290 / R600 | GDR400PP / GDR400PG | Pellistor | 0–100% LFL |
| R407C, R410A, R507A, R449A, R32, R134a, R404A, R1234ze, R1234yf, R454B, R454C | GDR400I3–I13 | NDIR | 0–2000 ppm |
| R407C, R410A, R507A, R449A, R32, R134a, R404A, R1234ze, R1234yf, R454B, R454C | GDR400S3–S13 | MOS | 0–1000 ppm |
Each detector is selected for one gas and range; this table does not describe a single multi-gas device. The shortened IC210, IC220 and IC250 codes have the same model prefix as IC25. I3–I13 and S3–S13 map to gases in the order listed in each row.
| Sensor | Integrated in the enclosure |
|---|---|
| Technologies | Electrochemical, NDIR, MOS or pellistor — gas- and code-specific |
| Display | None; LED indication |
| Primary signal | 4–20 mA |
| Communication | RS-485 / Modbus, Bluetooth — according to version |
| Voltage output | 1–5 V or 2–10 V — configuration-dependent; requires a 24 V DC supply. |
| Relays | Option: 2 alarm + 1 fault |
| Low-voltage supply | 11–30 V DC / 12–24 V AC (+10 / −15%) |
| Enclosure | IP67 |
| EC sensor — operating limits | EA / EAH: approximately 2 years; −40 to +50°C. |
| NDIR sensor — operating limits | Approximately 5 years in clean air. Codes IC25 / IC210 / IC220 / IC250 and I1–I9: −40 to +60°C. |
| Pellistor — operating limits | Approximately 5 years. PX: −40 to +60°C. |
| MOS sensor — operating limits | Approximately 5 years. Codes S3–S9 and SX: −20 to +50°C. |
| Buzzer | Only versions fitted with the relay board. |
Voltage output is an alternative analogue signal, not an additional independent channel. Communication, relays and buzzer availability depend on the version.
These are indicative clean-air lifespans, not warranty periods. Actual life depends on the gas, exposure, contamination and operating conditions. Interface and output availability depends on the complete ordering code.
GDR400 retains an integrated sensor like GDR300 while offering voltage and relay output options. GDR450 adds a local display.
Compare the five GDR detectors by sensor location, display and outputs.
Selection requires checking the gas, range, power supply and signal scaling. Detector location, alarm thresholds, gas response checks and calibration must follow the device requirements and site procedures. IP67 is not an ATEX or SIL designation. Measuring R290 or R600 in %LFL does not automatically approve the detector for installation in an explosive atmosphere.
Tell us the refrigerant, sensing location and required alarm response. We help select equipment for the installation.
Describe the installation requirements. Inquiry for: GDR400.