TECNOCONTROL · REFRIGERATION

GDR403 — remote-sensor refrigerant detector

A detector without a display, with its sensor installed separately from the main unit. Separating sensing and electronics helps position the detection point while retaining access for operation.

Tecnocontrol GDR403 — original manufacturer photographGDR403
Remote sensorUp to 3 m from electronics
LED indicationNo display
4–20 mAPrimary measurement signal
IP67Detector enclosure

Where GDR403 fits

For locations where the required sensing point differs from a convenient position for the main unit, without a need for a local screen.

Less accessible sensing points

Position the sensor near a potential leak source and the electronics at a more accessible location, within the permitted cable length.

Cold rooms and technical rooms

Separate the sensing point from the operating position. Conditions at both components must suit the selected version.

GDR403 operation

Sensor up to 3 m away

The sensor connection is limited to 3 m. The cable type and wiring depend on the sensor technology; the cable is not supplied.

Configuration at the electronics

There is no display. LEDs show status; Bluetooth-equipped versions allow local settings and diagnostics using the app.

Outputs to the installation

Select 4–20 mA and voltage, RS-485/Modbus and relay options for the required configuration. The sensor cable connector is not an Ethernet interface.

Cartridge and checks. The replaceable cartridge stores sensor identification and calibration data. Replacement requires the manufacturer’s procedure and suitably trained personnel. A bump test checks gas response; it does not replace calibration. Zero and span calibration must only be performed where permitted for the particular cartridge, using the correct gas and instructions. Check intervals depend on the sensor and operating conditions.

GDR403 gas-specific versions

Gas / refrigerantVersion codeTechnologyMeasuring range
NH₃GDR403EA / GDR403EAHElectrochemical0–1000 / 0–100 ppm
CO₂GDR403IC25 / IC210 / IC220 / IC250NDIR0–5000 ppm / 0–1 / 0–2 / 0–5 vol.%
R290 / R600GDR403I1 / GDR403I2NDIR0–100% LFL
R290 / R600GDR403PP / GDR403PGPellistor0–100% LFL
R407C, R410A, R507A, R449A, R32, R134a, R404A, R1234ze, R1234yf, R454B, R454CGDR403I3–I13NDIR0–2000 ppm
R407C, R410A, R507A, R449A, R32, R134a, R404A, R1234ze, R1234yf, R454B, R454CGDR403S3–S13MOS0–1000 ppm

Each detector is selected for one gas and range; this table does not describe a single multi-gas device. The shortened IC210, IC220 and IC250 codes have the same model prefix as IC25. I3–I13 and S3–S13 map to gases in the order listed in each row.

GDR403 technical specifications

SensorRemote, cable maximum 3 m
TechnologiesElectrochemical, NDIR, MOS or pellistor — gas- and code-specific
DisplayNone; LED indication
Primary signal4–20 mA
CommunicationRS-485 / Modbus, Bluetooth — according to version
Voltage output1–5 V or 2–10 V — configuration-dependent; requires a 24 V DC supply.
RelaysOption: 2 alarm + 1 fault
Low-voltage supply11–30 V DC / 12–24 V AC (+10 / −15%)
EnclosureIP67
EC sensor — operating limitsEA / EAH: approximately 2 years; −40 to +50°C.
NDIR sensor — operating limitsApproximately 5 years in clean air. Codes IC25 / IC210 / IC220 / IC250 and I1–I9: −40 to +60°C.
Pellistor — operating limitsApproximately 5 years. PX: −40 to +60°C.
MOS sensor — operating limitsApproximately 5 years. Codes S3–S9 and SX: −20 to +50°C.
BuzzerOnly versions fitted with the relay board.

Configuration notes

Voltage output is an alternative analogue signal, not an additional independent channel. Communication, relays and buzzer availability depend on the version.

These are indicative clean-air lifespans, not warranty periods. Actual life depends on the gas, exposure, contamination and operating conditions. Interface and output availability depends on the complete ordering code.

Place in the Refrigeration family

GDR403 is the remote-sensor counterpart to GDR400. Choose GDR453 when a remote sensor and a local LCD readout are both needed.

Which GDR model should I choose?

Compare the five GDR detectors by sensor location, display and outputs.

Compare Refrigeration models

Selection requires checking the gas, range, power supply and signal scaling. Detector location, alarm thresholds, gas response checks and calibration must follow the device requirements and site procedures. IP67 is not an ATEX or SIL designation. Measuring R290 or R600 in %LFL does not automatically approve the detector for installation in an explosive atmosphere. Install the sensor and electronics considering gas properties and airflow. Keep access for testing and servicing, respect the 3 m connection limit and use qualified installation personnel.

MES-EKO · Tecnocontrol

GDR403 — selection with MES-EKO

Tell us the refrigerant, sensing location and required alarm response. We help select equipment for the installation.

Selection review

  • Gas and operating conditionsRefrigerant, range, sensor technology and installation position.
  • Points and operationIntegrated or remote sensing, display and access for checks.
  • Signals and alarmsCompatibility of 4–20 mA, monitor, control panel and control outputs.

Request a Configuration

Describe the installation requirements. Inquiry for: GDR403.