Less accessible sensing points
Position the sensor near a potential leak source and the electronics at a more accessible location, within the permitted cable length.
A detector without a display, with its sensor installed separately from the main unit. Separating sensing and electronics helps position the detection point while retaining access for operation.
GDR403For locations where the required sensing point differs from a convenient position for the main unit, without a need for a local screen.
Position the sensor near a potential leak source and the electronics at a more accessible location, within the permitted cable length.
Separate the sensing point from the operating position. Conditions at both components must suit the selected version.
The sensor connection is limited to 3 m. The cable type and wiring depend on the sensor technology; the cable is not supplied.
There is no display. LEDs show status; Bluetooth-equipped versions allow local settings and diagnostics using the app.
Select 4–20 mA and voltage, RS-485/Modbus and relay options for the required configuration. The sensor cable connector is not an Ethernet interface.
Cartridge and checks. The replaceable cartridge stores sensor identification and calibration data. Replacement requires the manufacturer’s procedure and suitably trained personnel. A bump test checks gas response; it does not replace calibration. Zero and span calibration must only be performed where permitted for the particular cartridge, using the correct gas and instructions. Check intervals depend on the sensor and operating conditions.
| Gas / refrigerant | Version code | Technology | Measuring range |
|---|---|---|---|
| NH₃ | GDR403EA / GDR403EAH | Electrochemical | 0–1000 / 0–100 ppm |
| CO₂ | GDR403IC25 / IC210 / IC220 / IC250 | NDIR | 0–5000 ppm / 0–1 / 0–2 / 0–5 vol.% |
| R290 / R600 | GDR403I1 / GDR403I2 | NDIR | 0–100% LFL |
| R290 / R600 | GDR403PP / GDR403PG | Pellistor | 0–100% LFL |
| R407C, R410A, R507A, R449A, R32, R134a, R404A, R1234ze, R1234yf, R454B, R454C | GDR403I3–I13 | NDIR | 0–2000 ppm |
| R407C, R410A, R507A, R449A, R32, R134a, R404A, R1234ze, R1234yf, R454B, R454C | GDR403S3–S13 | MOS | 0–1000 ppm |
Each detector is selected for one gas and range; this table does not describe a single multi-gas device. The shortened IC210, IC220 and IC250 codes have the same model prefix as IC25. I3–I13 and S3–S13 map to gases in the order listed in each row.
| Sensor | Remote, cable maximum 3 m |
|---|---|
| Technologies | Electrochemical, NDIR, MOS or pellistor — gas- and code-specific |
| Display | None; LED indication |
| Primary signal | 4–20 mA |
| Communication | RS-485 / Modbus, Bluetooth — according to version |
| Voltage output | 1–5 V or 2–10 V — configuration-dependent; requires a 24 V DC supply. |
| Relays | Option: 2 alarm + 1 fault |
| Low-voltage supply | 11–30 V DC / 12–24 V AC (+10 / −15%) |
| Enclosure | IP67 |
| EC sensor — operating limits | EA / EAH: approximately 2 years; −40 to +50°C. |
| NDIR sensor — operating limits | Approximately 5 years in clean air. Codes IC25 / IC210 / IC220 / IC250 and I1–I9: −40 to +60°C. |
| Pellistor — operating limits | Approximately 5 years. PX: −40 to +60°C. |
| MOS sensor — operating limits | Approximately 5 years. Codes S3–S9 and SX: −20 to +50°C. |
| Buzzer | Only versions fitted with the relay board. |
Voltage output is an alternative analogue signal, not an additional independent channel. Communication, relays and buzzer availability depend on the version.
These are indicative clean-air lifespans, not warranty periods. Actual life depends on the gas, exposure, contamination and operating conditions. Interface and output availability depends on the complete ordering code.
GDR403 is the remote-sensor counterpart to GDR400. Choose GDR453 when a remote sensor and a local LCD readout are both needed.
Compare the five GDR detectors by sensor location, display and outputs.
Selection requires checking the gas, range, power supply and signal scaling. Detector location, alarm thresholds, gas response checks and calibration must follow the device requirements and site procedures. IP67 is not an ATEX or SIL designation. Measuring R290 or R600 in %LFL does not automatically approve the detector for installation in an explosive atmosphere. Install the sensor and electronics considering gas properties and airflow. Keep access for testing and servicing, respect the 3 m connection limit and use qualified installation personnel.
Tell us the refrigerant, sensing location and required alarm response. We help select equipment for the installation.
Describe the installation requirements. Inquiry for: GDR403.