Accessible refrigeration plant rooms
Local readings near refrigeration equipment; the detector position must suit the gas properties.
An integrated-sensor detector with an LCD for local concentration readings. It provides operation at the sensing point and sends readings and alarm states to the installation.
GDR450For points where personnel need a direct concentration readout and access to settings on site.
Local readings near refrigeration equipment; the detector position must suit the gas properties.
Monitoring a refrigeration circuit with a sensor selected for its refrigerant and an alarm strategy designed for the site.
The screen displays concentration and device messages. Keys provide menu access without opening the enclosure.
Bluetooth-equipped versions support app-based configuration and diagnostics. Functions and operating permissions must be agreed for the particular version.
Check 4–20 mA, voltage options, RS-485/Modbus and relays against the order code. A display does not mean that every version has the complete output set.
Cartridge and checks. The replaceable cartridge stores sensor identification and calibration data. Replacement requires the manufacturer’s procedure and suitably trained personnel. A bump test checks gas response; it does not replace calibration. Zero and span calibration must only be performed where permitted for the particular cartridge, using the correct gas and instructions. Check intervals depend on the sensor and operating conditions.
| Gas / refrigerant | Version code | Technology | Measuring range |
|---|---|---|---|
| NH₃ | GDR450EA / GDR450EAH | Electrochemical | 0–1000 / 0–100 ppm |
| CO₂ | GDR450IC25 / IC210 / IC220 / IC250 | NDIR | 0–5000 ppm / 0–1 / 0–2 / 0–5 vol.% |
| R290 / R600 | GDR450I1 / GDR450I2 | NDIR | 0–100% LFL |
| R290 / R600 | GDR450PX | Pellistor — on request | 0–100% LFL |
| R407C, R410A, R507A, R449A, R32, R134a, R404A, R1234ze, R1234yf, R454B, R454C | GDR450I3–I13 | NDIR | 0–2000 ppm |
| R407C, R410A, R507A, R449A, R32, R134a, R404A, R1234ze, R1234yf, R454B, R454C | GDR450S3–S13 | MOS | 0–1000 ppm |
Each detector is selected for one gas and range; this table does not describe a single multi-gas device. The shortened IC210, IC220 and IC250 codes have the same model prefix as IC25. I3–I13 and S3–S13 map to gases in the order listed in each row.
| Sensor | Integrated in the enclosure |
|---|---|
| Technologies | Electrochemical, NDIR, MOS or pellistor — gas- and code-specific |
| Display | LCD and local menu |
| Primary signal | 4–20 mA |
| Communication | RS-485 / Modbus, Bluetooth — according to version |
| Voltage output | 1–5 V or 2–10 V — configuration-dependent; requires a 24 V DC supply. |
| Relays | Option: 2 alarm + 1 fault |
| Low-voltage supply | 11–30 V DC / 12–24 V AC (+10 / −15%) |
| Enclosure | IP67 |
| EC sensor — operating limits | EA / EAH: approximately 2 years; −40 to +50°C. |
| NDIR sensor — operating limits | Approximately 5 years in clean air. Codes IC25 / IC210 / IC220 / IC250 and I1–I9: −40 to +60°C. |
| Pellistor — operating limits | Approximately 5 years. PX: −40 to +60°C. |
| MOS sensor — operating limits | Approximately 5 years. Codes S3–S9 and SX: −20 to +50°C. |
| Buzzer | Only versions fitted with the relay board. |
Voltage output is an alternative analogue signal, not an additional independent channel. Communication, relays and buzzer availability depend on the version.
These are indicative clean-air lifespans, not warranty periods. Actual life depends on the gas, exposure, contamination and operating conditions. Interface and output availability depends on the complete ordering code.
GDR450 combines a local display with an integrated sensor. GDR453 retains the local readout but places the sensor at a remote point.
Compare the five GDR detectors by sensor location, display and outputs.
Selection requires checking the gas, range, power supply and signal scaling. Detector location, alarm thresholds, gas response checks and calibration must follow the device requirements and site procedures. IP67 is not an ATEX or SIL designation. Measuring R290 or R600 in %LFL does not automatically approve the detector for installation in an explosive atmosphere.
Tell us the refrigerant, sensing location and required alarm response. We help select equipment for the installation.
Describe the installation requirements. Inquiry for: GDR450.