Plant rooms and enclosed equipment
Place the sensor near a potential leak point and the display at a convenient position within the 3 m connection limit.
A detector with an LCD and a remote sensor. Readings are viewed at the main unit while the sensor is placed at the required point, up to 3 m from the electronics.
GDR453Combines a separate sensing point with readings and a menu at an accessible location, where LED indication alone is insufficient.
Place the sensor near a potential leak point and the display at a convenient position within the 3 m connection limit.
Readings at the main unit and transmission to a monitor or alarm circuit according to the output configuration.
The LCD and keys are on the main unit. They provide status readout and detector configuration without moving the sensing point.
The cable must follow the instructions for the sensor technology. Do not treat the sensor connector as Ethernet or exceed the permitted cable length.
Check Bluetooth, RS-485/Modbus, relay and voltage-output availability against the ordered version. The primary measurement signal is 4–20 mA.
Cartridge and checks. The replaceable cartridge stores sensor identification and calibration data. Replacement requires the manufacturer’s procedure and suitably trained personnel. A bump test checks gas response; it does not replace calibration. Zero and span calibration must only be performed where permitted for the particular cartridge, using the correct gas and instructions. Check intervals depend on the sensor and operating conditions.
| Gas / refrigerant | Version code | Technology | Measuring range |
|---|---|---|---|
| NH₃ | GDR453EA / GDR453EAH | Electrochemical | 0–1000 / 0–100 ppm |
| CO₂ | GDR453IC25 / IC210 / IC220 / IC250 | NDIR | 0–5000 ppm / 0–1 / 0–2 / 0–5 vol.% |
| R290 / R600 | GDR453I1 / GDR453I2 | NDIR | 0–100% LFL |
| R290 / R600 | GDR453PX | Pellistor — on request | 0–100% LFL |
| R407C, R410A, R507A, R449A, R32, R134a, R404A, R1234ze, R1234yf, R454B, R454C | GDR453I3–I13 | NDIR | 0–2000 ppm |
| R407C, R410A, R507A, R449A, R32, R134a, R404A, R1234ze, R1234yf, R454B, R454C | GDR453S3–S13 | MOS | 0–1000 ppm |
Each detector is selected for one gas and range; this table does not describe a single multi-gas device. The shortened IC210, IC220 and IC250 codes have the same model prefix as IC25. I3–I13 and S3–S13 map to gases in the order listed in each row.
| Sensor | Remote, cable maximum 3 m |
|---|---|
| Technologies | Electrochemical, NDIR, MOS or pellistor — gas- and code-specific |
| Display | LCD and local menu |
| Primary signal | 4–20 mA |
| Communication | RS-485 / Modbus, Bluetooth — according to version |
| Voltage output | 1–5 V or 2–10 V — configuration-dependent; requires a 24 V DC supply. |
| Relays | Option: 2 alarm + 1 fault |
| Low-voltage supply | 11–30 V DC / 12–24 V AC (+10 / −15%) |
| Enclosure | IP67 |
| EC sensor — operating limits | EA / EAH: approximately 2 years; −40 to +50°C. |
| NDIR sensor — operating limits | Approximately 5 years in clean air. Codes IC25 / IC210 / IC220 / IC250 and I1–I9: −40 to +60°C. |
| Pellistor — operating limits | Approximately 5 years. PX: −40 to +60°C. |
| MOS sensor — operating limits | Approximately 5 years. Codes S3–S9 and SX: −20 to +50°C. |
| Buzzer | Only versions fitted with the relay board. |
Voltage output is an alternative analogue signal, not an additional independent channel. Communication, relays and buzzer availability depend on the version.
These are indicative clean-air lifespans, not warranty periods. Actual life depends on the gas, exposure, contamination and operating conditions. Interface and output availability depends on the complete ordering code.
GDR453 combines the remote sensing of GDR403 with a local display. GDR450 is the alternative when the sensor and electronics can share one location.
Compare the five GDR detectors by sensor location, display and outputs.
Selection requires checking the gas, range, power supply and signal scaling. Detector location, alarm thresholds, gas response checks and calibration must follow the device requirements and site procedures. IP67 is not an ATEX or SIL designation. Measuring R290 or R600 in %LFL does not automatically approve the detector for installation in an explosive atmosphere. Install the sensor and electronics considering gas properties and airflow. Keep access for testing and servicing, respect the 3 m connection limit and use qualified installation personnel.
Tell us the refrigerant, sensing location and required alarm response. We help select equipment for the installation.
Describe the installation requirements. Inquiry for: GDR453.