Chemical plants, petrochemical sites and refineries
Monitoring around equipment where flammable gases or vapours may be released.
Fixed detector for continuous monitoring of flammable gases and vapours in industrial installations. The GDS850P version uses a replaceable catalytic pellistor cartridge.
GDS850Monitoring around equipment where flammable gases or vapours may be released.
Flammable gas leak detection around fuel handling equipment and installations.
Monitoring at oil and gas installations, fuel terminals, fuel and gas storage facilities, and transfer points.
GDS850P versions cover the four gases shown below. On PX versions, select the gas in the menu. The detector reports concentration relative to the LFL of the selected gas.

Ambient gas reaches the pellistor through a sintered filter. The gas oxidises on the heated catalytic element. The resulting change in resistance provides a signal that depends on concentration.
The detector reports relative to the selected gas’s lower flammable limit (LFL). The pellistor requires oxygen and cannot selectively distinguish the constituents of a mixture. Contaminants may reduce the sensor response. Follow the calibration intervals specified by the manufacturer.
The display shows the concentration and the detector status: normal operation, alarm or fault. The manufacturer’s app connects to the detector via Bluetooth for local configuration, diagnostics and calibration without opening the enclosure.
| GDS850PX | 4–20 mA |
|---|---|
| GDS850PX-MB | 4–20 mA + RS-485 (Modbus) |
| GDS850PX-R-MB | 4–20 mA + RS-485 (Modbus) + standard relays |
| GDS850PX-RS-MB | 4–20 mA + RS-485 (Modbus) + safety relays |

Concentration signal to a suitable analogue input on a panel or controller. Check scaling and how the receiving system interprets fault and service signals.
Modbus on MB versions provides communication with a supervisory system. Match protocol support, the register map and bus settings to the installation.
Use this interface locally at the detector. Select a suitable wired output to communicate with the control panel.
Two alarm relays and one fault relay. Select the output type, alarm logic and permitted safety signal path for the detector code and installation design.
In SIL applications, the alarm circuit configuration and relay logic must follow the manufacturer’s instructions and meet the requirements of the safety function being designed.
Four cable entries help with cable routing. When selecting the control panel, check input type, power supply, fault handling and safety-function requirements.
| Sensing technology | Catalytic combustion (pellistor), diffusion measurement |
|---|---|
| Range and resolution | 0–100% LFL; 1% LFL |
| Accuracy and response time | ±5% of full scale; t₉₀ < 60 s |
| Warm-up time | 120 s |
| Stabilisation time | 2 h (minimum at first power-on) |
| Power supply and rated power | 11–30 V DC; 4.6 W |
| Operating conditions | −40 to +60 °C; 0.8–1.1 bar; up to 95% RH at 40 °C, non-condensing |
| Storage temperature | −20 to +55 °C |
| Enclosure protection | IP66 |
| Dimensions and weight | 148 × 190.5 × 112.5 mm; 3 kg |


Shields the sensing element from rain, dirt and direct wind.
The cartridge simplifies maintenance and can reduce downtime when replacing the sensor. Follow the manufacturer’s replacement procedure and applicable Ex requirements.
Expected sensor life is around 5 years in clean air, without contaminants that affect the sensing element. Actual service life depends on operating conditions.

For the GD*850P family: TÜV 22 ATEX 8793X and IECEx TUR 22.0003X, with markings II 2G Ex db IIC T6 Gb and II 2D Ex tb IIIC T80°C Db. Check the marking of the specific version against the installation area classification.
For the SIL-rated GDS version, the manufacturer specifies SIL 2 for hardware and SIL 3 for software under IEC/EN 61508. This does not establish SIL 3 for the detector or for the complete safety function.
EN 60079-29-1 coverage depends on the gas, order code and configuration. The X suffix refers to special conditions for safe use. Position the detector for the gas, likely leak sources and ventilation. Protect the sensor from high-pressure water jets, impact and excessive vibration. Do not open the enclosure in an explosive atmosphere. Plan maintenance around the temporary unavailability of the safety function during calibration.
We can help select the GDS850 for the hazard and determine how to connect it to the alarm system.
Tell us the target gas, installation location and alarm requirements. We can help select the device and plan the integration.