GDS850 — fixed industrial gas detector

Fixed detector for continuous monitoring of flammable gases and vapours in industrial installations. The GDS850P version uses a replaceable catalytic pellistor cartridge.

Tecnocontrol GDS850 — fixed industrial gas detectorGDS850
PellistorReplaceable sensor cartridge
0–100% LFLGDS850P measuring range
4–20 mAStandard output
IP66Enclosure protection
BluetoothLocal GDS850 operation

Industrial applications

Chemical plants, petrochemical sites and refineries

Monitoring around equipment where flammable gases or vapours may be released.

Power generation

Flammable gas leak detection around fuel handling equipment and installations.

Oil & gas, terminals and storage

Monitoring at oil and gas installations, fuel terminals, fuel and gas storage facilities, and transfer points.

Detected Gases

GDS850P versions cover the four gases shown below. On PX versions, select the gas in the menu. The detector reports concentration relative to the LFL of the selected gas.

  • CH₄Methane
  • H₂Hydrogen
  • C₃H₈Propane
  • C₄H₁₀n-butane

Technology, display and diagnostics

GDS850 display: normal operation, AL2 alarm and fault with an example fault code.

Diffusion measurement

Ambient gas reaches the pellistor through a sintered filter. The gas oxidises on the heated catalytic element. The resulting change in resistance provides a signal that depends on concentration.

Calibration for the selected gas

The detector reports relative to the selected gas’s lower flammable limit (LFL). The pellistor requires oxygen and cannot selectively distinguish the constituents of a mixture. Contaminants may reduce the sensor response. Follow the calibration intervals specified by the manufacturer.

Display and diagnostics

The display shows the concentration and the detector status: normal operation, alarm or fault. The manufacturer’s app connects to the detector via Bluetooth for local configuration, diagnostics and calibration without opening the enclosure.

GDS850PX output options

Example GDS850PX codes and outputs
GDS850PX4–20 mA
GDS850PX-MB4–20 mA + RS-485 (Modbus)
GDS850PX-R-MB4–20 mA + RS-485 (Modbus) + standard relays
GDS850PX-RS-MB4–20 mA + RS-485 (Modbus) + safety relays

GD/GDS family comparison

GD800 and GDS800 without a display or Bluetooth.
GD850 and GDS850 with a display and Bluetooth.

GD and GDS designations are not interchangeable. GD800 and GD850 are non-SIL versions. For SIL versions in the GDS800 and GDS850 lines, check certification scope and available options for the specific order code.

Communication and integration

GDS850 wiring diagram: standard 4–20 mA, MB option with Modbus RS-485, Bluetooth on the 850 version and R or RS options with alarm and fault relays.

Standard: 4–20 mA

Concentration signal to a suitable analogue input on a panel or controller. Check scaling and how the receiving system interprets fault and service signals.

MB option: RS-485 / Modbus

Modbus on MB versions provides communication with a supervisory system. Match protocol support, the register map and bus settings to the installation.

Bluetooth: local operation

Use this interface locally at the detector. Select a suitable wired output to communicate with the control panel.

R / RS options: relays

Two alarm relays and one fault relay. Select the output type, alarm logic and permitted safety signal path for the detector code and installation design.

In SIL applications, the alarm circuit configuration and relay logic must follow the manufacturer’s instructions and meet the requirements of the safety function being designed.

Four cable entries help with cable routing. When selecting the control panel, check input type, power supply, fault handling and safety-function requirements.

GDS850P technical specifications

GDS850P technical specifications
Sensing technologyCatalytic combustion (pellistor), diffusion measurement
Range and resolution0–100% LFL; 1% LFL
Accuracy and response time±5% of full scale; t₉₀ < 60 s
Warm-up time120 s
Stabilisation time2 h (minimum at first power-on)
Power supply and rated power11–30 V DC; 4.6 W
Operating conditions−40 to +60 °C; 0.8–1.1 bar; up to 95% RH at 40 °C, non-condensing
Storage temperature−20 to +55 °C
Enclosure protectionIP66
Dimensions and weight148 × 190.5 × 112.5 mm; 3 kg
Front and side views with dimensions of 24, 112.5, 80 and 190.5 mm.

Spare parts and accessories

GDS850 with weather protection and a replaceable sensor cartridge.

Weather protection

Shields the sensing element from rain, dirt and direct wind.

Replaceable sensor cartridge

The cartridge simplifies maintenance and can reduce downtime when replacing the sensor. Follow the manufacturer’s replacement procedure and applicable Ex requirements.

Expected sensor life is around 5 years in clean air, without contaminants that affect the sensing element. Actual service life depends on operating conditions.

Certification and installation requirements

GDS850: ATEX, IECEx, SIL 2 for hardware and SIL 3 for software on the SIL version, and EN 60079-29-1.

ATEX and IECEx

For the GD*850P family: TÜV 22 ATEX 8793X and IECEx TUR 22.0003X, with markings II 2G Ex db IIC T6 Gb and II 2D Ex tb IIIC T80°C Db. Check the marking of the specific version against the installation area classification.

SIL 2 hardware / SIL 3 software

For the SIL-rated GDS version, the manufacturer specifies SIL 2 for hardware and SIL 3 for software under IEC/EN 61508. This does not establish SIL 3 for the detector or for the complete safety function.

EN 60079-29-1 and installation requirements

EN 60079-29-1 coverage depends on the gas, order code and configuration. The X suffix refers to special conditions for safe use. Position the detector for the gas, likely leak sources and ventilation. Protect the sensor from high-pressure water jets, impact and excessive vibration. Do not open the enclosure in an explosive atmosphere. Plan maintenance around the temporary unavailability of the safety function during calibration.

Technical selection

GDS850 — selection and integration with MES-EKO

We can help select the GDS850 for the hazard and determine how to connect it to the alarm system.

What we review

  • Gas and operating conditionsIdentify the target gas and check whether a pellistor suits the operating conditions.
  • Detector versionSelect a version for the installation location and output requirements.
  • System integrationReview the connection to the control panel and how alarms will be signalled.

Selection and integration with MES-EKO

Tell us the target gas, installation location and alarm requirements. We can help select the device and plan the integration.