Cold rooms and cold storage
Leak monitoring near refrigeration circuits. The refrigerant and site arrangement determine the gas, range and sensing position.
Five GDR detectors for different sensing and operating arrangements, plus the SM400 system monitor. Match the sensor to the refrigerant and the outputs and alarms to the installation.


Start with the refrigerant and operating conditions, then select the sensor, installation position and system response.
Leak monitoring near refrigeration circuits. The refrigerant and site arrangement determine the gas, range and sensing position.
Detection near refrigeration units and pipe connections, with local readings or a separate monitor according to operating needs.
Select a version for ammonia, CO₂ or the refrigerant in use. Cleaning and operating conditions must meet device requirements.
Send readings and alarms to the building system through compatible outputs. Not every detector or sensor suits every application.
| Model | Type | Technology | Sensor | Display | Interfaces and outputs | Primary use |
|---|---|---|---|---|---|---|
| GDR300 | Fixed detector | EC / NDIR / MOS / pellistor¹ | Integrated | None, LEDs | 4–20 mA; Modbus RS-485; Bluetooth² | Readings at a panel or monitor |
| GDR400 | Fixed detector | EC / NDIR / MOS / pellistor¹ | Integrated | None, LEDs | 4–20 mA; voltage (1–5 / 2–10 V), Modbus RS-485, Bluetooth and relay options² | Local indication and alarm signalling |
| GDR450 | Fixed detector | EC / NDIR / MOS / pellistor¹ | Integrated | LCD | 4–20 mA; voltage (1–5 / 2–10 V), Modbus RS-485, Bluetooth and relay options² | Readings and operation at the detector |
| GDR403 | Fixed detector | EC / NDIR / MOS / pellistor¹ | Remote, up to 3 m | None, LEDs | 4–20 mA; voltage (1–5 / 2–10 V), Modbus RS-485, Bluetooth and relay options² | Separating sensing from electronics |
| GDR453 | Fixed detector | EC / NDIR / MOS / pellistor¹ | Remote, up to 3 m | LCD | 4–20 mA; voltage (1–5 / 2–10 V), Modbus RS-485, Bluetooth and relay options² | Remote sensing with accessible local readings |
| SM400 | System monitor | No measurement | None | 3.5-inch touch | 4 × 4–20 mA inputs; 4 relays; Modbus RS-485; Bluetooth | Combined readings and alarm signalling |
¹ Technology depends on the gas and code; it does not mean four sensors in one device. EC: electrochemical; NDIR: infrared; MOS: semiconductor. Pellistor on GDR450/GDR453: PX version on request. ² Equipment and options depend on the order code. GDR300 does not have voltage outputs, relays or an audible sounder.

For installations where readings are viewed at a control panel and the detector is required to transmit a measurement signal without a local screen.

A choice of signal options when a local screen is unnecessary but readings or alarms need to be sent to the installation.

For points where personnel need a direct concentration readout and access to settings on site.

For locations where the required sensing point differs from a convenient position for the main unit, without a need for a local screen.

Combines a separate sensing point with readings and a menu at an accessible location, where LED indication alone is insufficient.
Electrochemical EA sensors: 0–1000 ppm; EAH: 0–100 ppm. Select for the ammonia installation and required range.
NDIR versions IC25, IC210, IC220 and IC250: respectively 0–5000 ppm, 0–1, 0–2 or 0–5 vol.%.
Propane and n-butane: NDIR I1/I2 or an appropriate pellistor, 0–100% LFL. LCD models use a PX pellistor version selected on request.
NDIR I3–I13 versions: 0–2000 ppm; MOS S3–S13: 0–1000 ppm. Technology and calibration must match the particular refrigerant.
Availability depends on the model, sensor and specific version code. These are examples, not a list of refrigerants that every device supports.
These are not detectors measuring all listed gases simultaneously. Each unit has a sensor and range selected for one gas. Model pages list the version codes.
Measuring R290 or R600 in %LFL does not automatically approve the detector for installation in an explosive atmosphere.
Indicative sensor life. EC: approximately 2 years; NDIR, pellistor and MOS: approximately 5 years in clean air. These are not warranty periods: gas, exposure, contamination and use affect actual life. Temperature limits depend on the cartridge code and are listed on the model pages.

A system monitor displaying readings and alarms from up to four 4–20 mA detectors. Its touchscreen provides a system overview; SM400 does not measure gas itself.
Select compatible detectors, signal scaling and required alarms. SM504/SM508 are separate versions with Modbus inputs.
Positioning follows the refrigerant properties, potential leak sources and airflow. A remote sensor separates sensing and operation but has a 3 m cable limit.
Check the 4–20 mA output type, scaling, power supply and fault interpretation at the monitor or panel. RS-485 requires compatible protocol settings and addresses.
Select thresholds, logic and actuator control for the site. Response checks and calibrations follow the procedures for the specific device.
GDR maintenance. Replaceable cartridges store identification and calibration data. Operation, diagnostics and replacement follow the manufacturer’s procedure; Bluetooth is available only on suitably equipped versions. A bump test confirms gas response; zero and span calibration are separate, cartridge-dependent operations. Intervals depend on the sensor and site conditions.
Interface and output availability depends on the complete ordering code.
Tell us the refrigerant, sensing location and required alarm response. We help select equipment for the installation.
Describe the installation requirements. Inquiry for: Tecnocontrol Refrigeration.