Plant-room entrance overview
Display readings from detectors inside the monitored room at a position convenient for personnel.
A system monitor displaying readings and alarms from up to four 4–20 mA detectors. Its touchscreen provides a system overview; SM400 does not measure gas itself.
SM400A shared viewing point for detector readings, for example near a technical-room entrance. Gases and ranges depend on the connected detectors.
Display readings from detectors inside the monitored room at a position convenient for personnel.
Collect signals from up to four analogue detectors and transmit alarm and fault states through relay outputs.
SM400 receives four analogue signals. Each input requires the correct detector assignment, scaling and interpretation of measurement and fault states.
The colour screen shows readings and channel states, providing an overview without visiting every detector.
Four relays provide three alarm outputs and one fault output. The manufacturer specifies Modbus RS-485 RTU client/server and Bluetooth for system operation.
Configure alarm thresholds, relay assignments and Modbus settings to match the detectors and installation design. Bluetooth supports local setup and status readout; it does not replace the wired alarm path.
| Role | System monitor; no built-in gas sensor |
|---|---|
| Inputs | 4 × 4–20 mA |
| Display | 3.5-inch colour touchscreen |
| Relay outputs | 4: 3 alarm + 1 fault |
| Communication | Modbus RS-485 RTU client/server, Bluetooth |
| Power supply | 12–24 V DC |
| Enclosure | IP67 |
| Relay contact rating | 2 A / 30 V DC |
SM400 has no gas sensor or measuring range of its own. Do not apply the input capacities of SM504/SM508 to this model.
SM400 works with detectors rather than replacing them. SM504 and SM508 with Modbus inputs are different versions; SM400 is not an eight-detector monitor.
Before connection, check 4–20 mA input/output types, scaling, detector power requirements and fault interpretation. The monitor does not replace a complete safety procedure. No ATEX or SIL certification is claimed for it.
Tell us the refrigerant, sensing location and required alarm response. We help select equipment for the installation.
Describe the installation requirements. Inquiry for: SM400.