Chemical and petrochemical plants
Leak monitoring for the toxic or flammable gases supported by the selected version, with sensor technology matched to the hazard and cross-sensitivities.
Local concentration readings and a signal to the gas control panel in one detector. Select an electrochemical, NDIR or catalytic version for the particular gas, range and installation conditions.
TS593Each unit is selected for one gas or a specified mixture. The applications do not imply simultaneous measurement of every gas.
Leak monitoring for the toxic or flammable gases supported by the selected version, with sensor technology matched to the hazard and cross-sensitivities.
For points requiring on-site readings and signals to an alarm system; select the gas and thresholds for the installation.
Detection near equipment and pipe connections. Methane, LPG, hydrogen or another gas requires the correct version and calibration.
TS593EO monitors O₂; TS593IC2/IC2-H monitors CO₂, for example around fermentation and gas storage. The sensors are not interchangeable.

The backlit 8 × 2 character screen shows the gas, concentration and sensor status messages. Staff can inspect the sensing point without relying solely on the control panel display.
Green ON indicates normal operation; red ALARM provides local alarm indication for the detector version; yellow FAULT indicates a condition requiring diagnostics. Messages and behaviour depend on the version.
Operate F1/F2 through the glass using the supplied magnetic key. Coded sequences provide access to tests and calibration without opening the enclosure.
The LED threshold is specified for the particular version. Its operation also depends on the DIP-switch configuration; the versions described allow this indication to be enabled or disabled. TS593 does not provide a universal, freely programmable set of alarm thresholds. The appropriate alarm thresholds for the complete system are configured in the gas control panel.
| TS593EA / TS593EA-H — NH₃ | 50 ppm |
|---|---|
| TS593EC-S / TS593EC-H — CO | 200 ppm |
| TS593EH — H₂S | 20 ppm |
| TS593IM — CH₄ | 20% LFL |
| TS593IC2 — CO₂ | 0.5 vol.% |
| TS593IC2-H — CO₂ | 2500 ppm |
TS593 alone does not identify the gas or sensor technology. The full codes below identify the individual versions; the measuring range is not the sensor’s maximum permitted exposure.
| Version code | Gas | Technology | Range | Resolution / accuracy | Conditions and limitations |
|---|---|---|---|---|---|
| TS593EA | NH₃ — ammonia | Electrochemical | 0–300 ppm | Resolution: 1 ppm | −20…+40°C T90: <180 s |
| TS593EA-H | NH₃ — ammonia | Electrochemical | 0–300 ppm | Resolution: 1 ppm | −20…+40°C. Cartridge for environments with other contaminants; assess cross-sensitivities during selection. T90: <120 s² |
| TS593EC-S | CO — carbon monoxide | Electrochemical | 0–300 ppm | Resolution: 1 ppm | −20…+50°C T90: <60 s |
| TS593EC-H | CO — carbon monoxide | Electrochemical | 0–300 ppm | Resolution: 1 ppm | −20…+50°C. Cartridge for environments with other contaminants; assess cross-sensitivities during selection. T90: ≤40 s |
| TS593ES | SO₂ — sulphur dioxide | Electrochemical | 0–20 ppm | Resolution: 0.1 ppm | −10…+50°C T90: ≤75 s |
| TS593EH | H₂S — hydrogen sulphide | Electrochemical | 0–100 ppm | Resolution: 1 ppm | −10…+40°C T90: ≤50 s |
| TS593EHCN | HCN — hydrogen cyanide | Electrochemical | 0–10 ppm | Resolution: 0.1 ppm | 0…+50°C T90: ≤3 min |
| TS593EN | NO — nitric oxide | Electrochemical | 0–100 ppm | Resolution: 1 ppm | −20…+50°C T90: ≤60 s |
| TS593EN2 | NO₂ — nitrogen dioxide | Electrochemical | 0–30 ppm | Resolution: 1 ppm | −20…+50°C T90: ≤60 s |
| TS593EO | O₂ — oxygen | Electrochemical | 0–25 vol.% | Accuracy: ±2% of signal in air | −20…+50°C. Oxygen version; it does not directly measure inert gas. T90: <30 s |
| Version code | Gas | Technology | Range | Resolution / accuracy | Conditions and limitations |
|---|---|---|---|---|---|
| TS593IM | CH₄ — methane | NDIR | 0–100% LFL | See NDIR performance note¹ | −10…+50°C. Calibrated for the stated gas or mixture. T90: <50 s |
| TS593IG | LPG — liquefied petroleum gas | NDIR | 0–100% LFL | See NDIR performance note¹ | −10…+50°C. Calibrated for the stated gas or mixture. T90: <50 s |
| TS593IB | Petrol vapours | NDIR | 0–100% LFL | See NDIR performance note¹ | −10…+50°C. Calibrated for the stated gas or mixture. T90: <50 s |
| TS593IC2 | CO₂ — carbon dioxide | NDIR | 0–5 vol.% | LCD resolution: 0.01 vol.% (±1 digit) | −10…+50°C T90: <50 s |
| TS593IC2-H | CO₂ — carbon dioxide | NDIR | 0–5000 ppm | LCD resolution: 1 ppm (±1 digit) | −10…+50°C T90: <50 s |
| Version code | Gas | Technology | Range | Resolution / accuracy | Conditions and limitations |
|---|---|---|---|---|---|
| TS593PE | C₂H₂ — acetylene | Catalytic — pellistor | 0–100% LFL | Accuracy: ±10% | −10…+50°C. Requires oxygen; linearity is specified up to 60% LFL. T90: <60 s |
| TS593PS | Styrene | Catalytic — pellistor | 0–100% LFL | Accuracy: ±10% | −10…+50°C. Requires oxygen; linearity is specified up to 60% LFL. T90: <60 s |
| TS593PX-H | CH₄, H₂, C₃H₈ or n-C₄H₁₀ | Catalytic — pellistor | 0–100% LFL | Accuracy: ±10% | −10…+50°C. One selected gas and the matching calibration; requires oxygen. T90: <60 s |
¹ For TS593IM, resolution is specified as ±1% LFL. This is not an accuracy specification for other versions. TS593IM/IG/IB are not hydrogen versions. Pellistors have linearity up to 60% LFL and require oxygen.
TS593PX-H is configured for a selected gas; the listed gases are examples, not simultaneous measurement channels. Specify the calibration gas when ordering. The listed temperature limits apply to the particular sensors.
T90 is the time to reach 90% of the response. Values apply to the specified versions and cartridges, not the entire family. ² For TS593EA-H, the manufacturer gives a value calculated from 5 minutes of exposure.
| Power supply | 12–24 V DC (−10 / +15%) |
|---|---|
| Power consumption | 2 W: E, EO, IM/IG/IB and IC2/IC2-H versions. |
| Output | 1 linear 4–20 mA output; three-wire connection. |
| Display and operation | Backlit 8 × 2 character LCD, 3 LEDs, F1/F2 operated with a magnetic key. |
| Enclosure | Flameproof enclosure with a glass window and a downward-facing cartridge holder. |
| Protection rating | IP65 |
| Ex marking | II 2G Ex db IIC T6 Gb |
| ATEX certificate | CESI 03 ATEX 323 X |
| Operating humidity | E and EO: 15–90% RH; NDIR and pellistor: 10–90% RH; non-condensing. |
| Operating temperature | Sensor-code-specific — see the version tables above. |
| Dimensions and weight | 190 × 105 × 83 mm; 3 kg |
| Installation | Vertical, sensor holder facing down; position for the gas and ventilation. |
| NDIR — warm-up | TS593IM/IG/IB and TS593IC2/IC2-H: approximately 60 s; the LCD shows a WARM UP countdown and the yellow FAULT LED flashes. |
| NDIR — optimum stability | TS593IM/IG/IB and TS593IC2/IC2-H: approximately 1 hour of continuous operation. This is a separate stage from initial warm-up. |
Check the power supply, output load and sensor conditions for the ordered version. IP65 and the Ex marking do not override the cartridge’s temperature and humidity limits.
These times apply only to the listed NDIR versions, not electrochemical or catalytic versions. They do not replace the required operating period before calibration.
The magnetic key starts the zero and calibration procedures appropriate to the version. TS593EO uses calibration in air; do not treat this as zeroing a toxic gas detector.
A test gas checks detector response; calibration adjusts the readings. Trained personnel must use the correct gas mixture and coordinate the control panel response because the test signal can activate alarms.
The factory-calibrated, replaceable cartridge contains the sensor and its identification and calibration data. Replacement follows the manufacturer’s procedure. Set check intervals for the version, operating conditions and site requirements.

Original Tecnocontrol magnetic key for operation through the enclosure window. The specified procedures can be carried out without opening the cover.
Indicative clean-air periods: most listed toxic gas and O₂ sensors — 2 years; TS593EC-S — 3 years; pellistor — approximately 5 years. NDIR sensor MTBF of over 5 years is neither a lifetime guarantee nor a replacement interval. Contamination and exposure can shorten these periods.
A gas response test is not calibration. Checking zero, checking readings with a reference gas, and any zero adjustment or span calibration are separate operations carried out using the cartridge-specific procedure. O₂ requires its specific calibration-in-air procedure.
operational checks every 6 or 12 months; this is not a common sensor replacement interval.
checks at least annually, or more frequently — every 3–6 months — depending on conditions and safety requirements. Recommended NDIR calibration interval: 12 months.
checks at least annually, or more frequently — every 6 months — depending on conditions. Recommended NDIR calibration interval: 12 months.
checks at least annually, or more frequently — every 3–6 months — depending on conditions and safety requirements; zero adjustment and calibration follow the relevant cartridge procedure.
Qualified personnel must carry out checks and adjustments using Ex safety procedures and coordinating the response of the control panel and actuators. Do not wait until the next inspection if a fault or suspected measurement error occurs.
Select the supply, polarity, output load and cable size. Output load: 50 Ω at 12 V DC (−10%) and 500 Ω at 24 V DC (−10%); allow for voltage drop.
The panel must interpret the cartridge’s ppm, vol.% or %LFL scale and its start-up, calibration and fault signals. The local ALARM LED is not a relay output.
The linear 4–20 mA output sends readings to the control panel. Relay control and communication with a supervisory system are provided by suitably selected alarm system components.
A 0 mA signal is outside the normal 4–20 mA range; it is not a valid zero-concentration reading. The nominal output at the lower end of the linear measuring scale is 4 mA.
DIP configuration, cartridge data or operation, connection or compatibility errors produce 0 mA, with the yellow FAULT LED on and green ON LED off.
0 mA with both yellow and green LEDs on; possible cartridge fault.
over 24 mA with all LEDs on — a possible cartridge fault or a concentration above the measuring range.
a cartridge service-life warning does not itself mean that the output switches to 0 mA. A yellow LED flash every 4 s with green ON requires assessment and cartridge replacement using the service procedure; continued readings do not establish correct operation.
0 mA can also occur during calibration procedures. The control panel must recognise faults correctly and distinguish them from measurements and coordinated service states; match the indication details and DIP settings to the version.

CE408 accepts 4–20 mA detector signals. Before connecting TS593, verify the supply, load, scaling and channel configuration.
View details — CE408The II 2G Ex db IIC T6 Gb marking and CESI 03 ATEX 323 X certificate apply to the specified versions and compatible enclosure/sensor configuration. Selection for gas zones 1 or 2 requires checking the nameplate, gas, temperature and certificate conditions.
Use appropriately certified cable entries and stopping plugs. Do not modify the enclosure or sensor holder. Do not open the unit while energised; installation and servicing require suitable qualifications and procedures.
Explosion protection certification does not imply SIL certification or automatic compliance of the complete alarm system. Check the response of the panel, signalling equipment and actuators as well.
Tell us the gas, range, installation area classification and required alarm response. We help select the TS593 version and a suitable control panel.
Describe the installation requirements. Inquiry for: TS593.