TECNOCONTROL · INDUSTRIAL GAS DETECTION

TS593 — Industrial Gas Detector with Display

Local concentration readings and a signal to the gas control panel in one detector. Select an electrochemical, NDIR or catalytic version for the particular gas, range and installation conditions.

TS593 with LCD — illustrative methane versionTS593
8 × 2 LCDBacklit display
Local readoutConcentration at the installation
4–20 mALinear analogue output
Magnetic operationCalibration without opening
Replaceable cartridgeFactory-calibrated sensor
ATEXII 2G Ex db IIC T6 Gb

Industrial Applications

Each unit is selected for one gas or a specified mixture. The applications do not imply simultaneous measurement of every gas.

Chemical and petrochemical plants

Leak monitoring for the toxic or flammable gases supported by the selected version, with sensor technology matched to the hazard and cross-sensitivities.

Manufacturing and power facilities

For points requiring on-site readings and signals to an alarm system; select the gas and thresholds for the installation.

Gas storage and distribution

Detection near equipment and pipe connections. Methane, LPG, hydrogen or another gas requires the correct version and calibration.

Oxygen and carbon dioxide

TS593EO monitors O₂; TS593IC2/IC2-H monitors CO₂, for example around fermentation and gas storage. The sensors are not interchangeable.

Display, Operation and Diagnostics

TS593 — original view of the electronics and sensor cartridge holder
Original TS593 construction view. Opening the unit is subject to Ex safety requirements.

LCD and on-site readings

The backlit 8 × 2 character screen shows the gas, concentration and sensor status messages. Staff can inspect the sensing point without relying solely on the control panel display.

Three LED indicators

Green ON indicates normal operation; red ALARM provides local alarm indication for the detector version; yellow FAULT indicates a condition requiring diagnostics. Messages and behaviour depend on the version.

F1/F2 and magnetic key

Operate F1/F2 through the glass using the supplied magnetic key. Coded sequences provide access to tests and calibration without opening the enclosure.

Local ALARM LED versus system alarms.

The LED threshold is specified for the particular version. Its operation also depends on the DIP-switch configuration; the versions described allow this indication to be enabled or disabled. TS593 does not provide a universal, freely programmable set of alarm thresholds. The appropriate alarm thresholds for the complete system are configured in the gas control panel.

TS593EA / TS593EA-H — NH₃50 ppm
TS593EC-S / TS593EC-H — CO200 ppm
TS593EH — H₂S20 ppm
TS593IM — CH₄20% LFL
TS593IC2 — CO₂0.5 vol.%
TS593IC2-H — CO₂2500 ppm

Versions and Measuring Ranges

TS593 alone does not identify the gas or sensor technology. The full codes below identify the individual versions; the measuring range is not the sensor’s maximum permitted exposure.

Electrochemical — Toxic Gases and Oxygen

Version codeGasTechnologyRangeResolution / accuracyConditions and limitations
TS593EANH₃ — ammoniaElectrochemical0–300 ppmResolution: 1 ppm−20…+40°C
T90: <180 s
TS593EA-HNH₃ — ammoniaElectrochemical0–300 ppmResolution: 1 ppm−20…+40°C. Cartridge for environments with other contaminants; assess cross-sensitivities during selection.
T90: <120 s²
TS593EC-SCO — carbon monoxideElectrochemical0–300 ppmResolution: 1 ppm−20…+50°C
T90: <60 s
TS593EC-HCO — carbon monoxideElectrochemical0–300 ppmResolution: 1 ppm−20…+50°C. Cartridge for environments with other contaminants; assess cross-sensitivities during selection.
T90: ≤40 s
TS593ESSO₂ — sulphur dioxideElectrochemical0–20 ppmResolution: 0.1 ppm−10…+50°C
T90: ≤75 s
TS593EHH₂S — hydrogen sulphideElectrochemical0–100 ppmResolution: 1 ppm−10…+40°C
T90: ≤50 s
TS593EHCNHCN — hydrogen cyanideElectrochemical0–10 ppmResolution: 0.1 ppm0…+50°C
T90: ≤3 min
TS593ENNO — nitric oxideElectrochemical0–100 ppmResolution: 1 ppm−20…+50°C
T90: ≤60 s
TS593EN2NO₂ — nitrogen dioxideElectrochemical0–30 ppmResolution: 1 ppm−20…+50°C
T90: ≤60 s
TS593EOO₂ — oxygenElectrochemical0–25 vol.%Accuracy: ±2% of signal in air−20…+50°C. Oxygen version; it does not directly measure inert gas.
T90: <30 s

NDIR — Selected Flammable Gases and CO₂

Version codeGasTechnologyRangeResolution / accuracyConditions and limitations
TS593IMCH₄ — methaneNDIR0–100% LFLSee NDIR performance note¹−10…+50°C. Calibrated for the stated gas or mixture.
T90: <50 s
TS593IGLPG — liquefied petroleum gasNDIR0–100% LFLSee NDIR performance note¹−10…+50°C. Calibrated for the stated gas or mixture.
T90: <50 s
TS593IBPetrol vapoursNDIR0–100% LFLSee NDIR performance note¹−10…+50°C. Calibrated for the stated gas or mixture.
T90: <50 s
TS593IC2CO₂ — carbon dioxideNDIR0–5 vol.%LCD resolution: 0.01 vol.% (±1 digit)−10…+50°C
T90: <50 s
TS593IC2-HCO₂ — carbon dioxideNDIR0–5000 ppmLCD resolution: 1 ppm (±1 digit)−10…+50°C
T90: <50 s

Pellistor — Flammable Gases and Vapours

Version codeGasTechnologyRangeResolution / accuracyConditions and limitations
TS593PEC₂H₂ — acetyleneCatalytic — pellistor0–100% LFLAccuracy: ±10%−10…+50°C. Requires oxygen; linearity is specified up to 60% LFL.
T90: <60 s
TS593PSStyreneCatalytic — pellistor0–100% LFLAccuracy: ±10%−10…+50°C. Requires oxygen; linearity is specified up to 60% LFL.
T90: <60 s
TS593PX-HCH₄, H₂, C₃H₈ or n-C₄H₁₀Catalytic — pellistor0–100% LFLAccuracy: ±10%−10…+50°C. One selected gas and the matching calibration; requires oxygen.
T90: <60 s

¹ For TS593IM, resolution is specified as ±1% LFL. This is not an accuracy specification for other versions. TS593IM/IG/IB are not hydrogen versions. Pellistors have linearity up to 60% LFL and require oxygen.

TS593PX-H is configured for a selected gas; the listed gases are examples, not simultaneous measurement channels. Specify the calibration gas when ordering. The listed temperature limits apply to the particular sensors.

T90 is the time to reach 90% of the response. Values apply to the specified versions and cartridges, not the entire family. ² For TS593EA-H, the manufacturer gives a value calculated from 5 minutes of exposure.

TS593 Technical Specifications

Power supply12–24 V DC (−10 / +15%)
Power consumption2 W: E, EO, IM/IG/IB and IC2/IC2-H versions.
Output1 linear 4–20 mA output; three-wire connection.
Display and operationBacklit 8 × 2 character LCD, 3 LEDs, F1/F2 operated with a magnetic key.
EnclosureFlameproof enclosure with a glass window and a downward-facing cartridge holder.
Protection ratingIP65
Ex markingII 2G Ex db IIC T6 Gb
ATEX certificateCESI 03 ATEX 323 X
Operating humidityE and EO: 15–90% RH; NDIR and pellistor: 10–90% RH; non-condensing.
Operating temperatureSensor-code-specific — see the version tables above.
Dimensions and weight190 × 105 × 83 mm; 3 kg
InstallationVertical, sensor holder facing down; position for the gas and ventilation.
NDIR — warm-upTS593IM/IG/IB and TS593IC2/IC2-H: approximately 60 s; the LCD shows a WARM UP countdown and the yellow FAULT LED flashes.
NDIR — optimum stabilityTS593IM/IG/IB and TS593IC2/IC2-H: approximately 1 hour of continuous operation. This is a separate stage from initial warm-up.

Check the power supply, output load and sensor conditions for the ordered version. IP65 and the Ex marking do not override the cartridge’s temperature and humidity limits.

These times apply only to the listed NDIR versions, not electrochemical or catalytic versions. They do not replace the required operating period before calibration.

Calibration, Cartridges and Maintenance

Adjustment without opening

The magnetic key starts the zero and calibration procedures appropriate to the version. TS593EO uses calibration in air; do not treat this as zeroing a toxic gas detector.

Response checks and calibration

A test gas checks detector response; calibration adjusts the readings. Trained personnel must use the correct gas mixture and coordinate the control panel response because the test signal can activate alarms.

Cartridge and maintenance plan

The factory-calibrated, replaceable cartridge contains the sensor and its identification and calibration data. Replacement follows the manufacturer’s procedure. Set check intervals for the version, operating conditions and site requirements.

Tecnocontrol magnetic key for F1 and F2 operation

Original Tecnocontrol magnetic key for operation through the enclosure window. The specified procedures can be carried out without opening the cover.

Indicative clean-air periods: most listed toxic gas and O₂ sensors — 2 years; TS593EC-S — 3 years; pellistor — approximately 5 years. NDIR sensor MTBF of over 5 years is neither a lifetime guarantee nor a replacement interval. Contamination and exposure can shorten these periods.

Periodic checks by technology.

A gas response test is not calibration. Checking zero, checking readings with a reference gas, and any zero adjustment or span calibration are separate operations carried out using the cartridge-specific procedure. O₂ requires its specific calibration-in-air procedure.

  • TS593E and TS593EO

    operational checks every 6 or 12 months; this is not a common sensor replacement interval.

  • TS593IM/IG/IB

    checks at least annually, or more frequently — every 3–6 months — depending on conditions and safety requirements. Recommended NDIR calibration interval: 12 months.

  • TS593IC2/IC2-H

    checks at least annually, or more frequently — every 6 months — depending on conditions. Recommended NDIR calibration interval: 12 months.

  • TS593PE/PS/PX-H

    checks at least annually, or more frequently — every 3–6 months — depending on conditions and safety requirements; zero adjustment and calibration follow the relevant cartridge procedure.

Qualified personnel must carry out checks and adjustments using Ex safety procedures and coordinating the response of the control panel and actuators. Do not wait until the next inspection if a fault or suspected measurement error occurs.

Integration with a Gas Detection System

  1. TS593
  2. 4–20 mA signal
  3. Gas control panel
  4. Signalling / actuators

Electrical compatibility

Select the supply, polarity, output load and cable size. Output load: 50 Ω at 12 V DC (−10%) and 500 Ω at 24 V DC (−10%); allow for voltage drop.

Scaling and fault states

The panel must interpret the cartridge’s ppm, vol.% or %LFL scale and its start-up, calibration and fault signals. The local ALARM LED is not a relay output.

The linear 4–20 mA output sends readings to the control panel. Relay control and communication with a supervisory system are provided by suitably selected alarm system components.

Output diagnostics — E, EO, IM, IC2 and PX-H versions.

A 0 mA signal is outside the normal 4–20 mA range; it is not a valid zero-concentration reading. The nominal output at the lower end of the linear measuring scale is 4 mA.

  • ERROR DIP / ERROR DATA / ERROR LINE

    DIP configuration, cartridge data or operation, connection or compatibility errors produce 0 mA, with the yellow FAULT LED on and green ON LED off.

  • FAULT−

    0 mA with both yellow and green LEDs on; possible cartridge fault.

    FAULT+

    over 24 mA with all LEDs on — a possible cartridge fault or a concentration above the measuring range.

  • EXPIRED / periodic FAULT flashing

    a cartridge service-life warning does not itself mean that the output switches to 0 mA. A yellow LED flash every 4 s with green ON requires assessment and cartridge replacement using the service procedure; continued readings do not establish correct operation.

0 mA can also occur during calibration procedures. The control panel must recognise faults correctly and distinguish them from measurements and coordinated service states; match the indication details and DIP settings to the version.

Certification and Installation Conditions

ATEX and the correct version

The II 2G Ex db IIC T6 Gb marking and CESI 03 ATEX 323 X certificate apply to the specified versions and compatible enclosure/sensor configuration. Selection for gas zones 1 or 2 requires checking the nameplate, gas, temperature and certificate conditions.

Ex installation and maintenance

Use appropriately certified cable entries and stopping plugs. Do not modify the enclosure or sensor holder. Do not open the unit while energised; installation and servicing require suitable qualifications and procedures.

Scope of the safety function

Explosion protection certification does not imply SIL certification or automatic compliance of the complete alarm system. Check the response of the panel, signalling equipment and actuators as well.

MES-EKO · Tecnocontrol

TS593 — selection with MES-EKO

Tell us the gas, range, installation area classification and required alarm response. We help select the TS593 version and a suitable control panel.

Selection review

  • Gas and operating conditionsGas, range, sensor technology and permitted operating conditions.
  • Points and operationLocal readings, area classification and access for testing and servicing.
  • Signals and alarmsPower supply, 4–20 mA scaling, control panel and alarm logic.

Request a Configuration

Describe the installation requirements. Inquiry for: TS593.